Figure 10
5.4.7 The LCD will display the
measured Air Volume in
CFM (cubic feet per minute)
(Fig. 10).
5.4.8 To repeat this measurement
or IF YOU WISH TO MEA-
SURE ADDITIONAL
OPENINGS, press ENTER
and repeat steps 5.4.2-5.4.7.
Measure each opening as
previously described in
order to obtain an overall
average reading. At the
completion of each test, the
sum of ALL measurements
can be displayed by pressing
the
Ç button.
*When moving probe along
the grills borders (A,D) keep
the probe halfway out of the
grill.
A
B
C
D
Note: Aim at getting an average
reading from all available open-
ings. (see next step)
5.5 Measuring Capacity
IMPORTANT NOTE:
Before you begin to measure capacity,
press the MODE button until you reach the HUMIDITY
mode. Put the probe in front of the inlet air (or ambient
room humidity) so that the sensors cover is facing AWAY
FROM THE INLET GRILL and wait until the humidity meas-
urement stabilizes (this also allows the TEMP measure-
ment to stabilize). DO NOT place the probe at the output
grill because it will take a long time (10 minutes) to return to
normal room temperature and humidity conditions!
Page 10